  Datasheet File OCR Text:
 Voltage Sensitive Relays
WILMARTM Protective Relays - WOUV DC Series, Over/Undervoltage
Function:
* ANSI/IEEE C37.90-1978
The relay will energize at normal voltage conditions. The normally open contacts will close, and the normally closed contacts will open. The relay will de-energize during over or undervoltage conditions. Reset is automatic when the voltage returns to normal.
PS TRI L S EWS A MIN SCR TER - 32 #6
2 13/16
2.0
(+) (-)
3
3
3 7/ 8
1/
Drop-Out Time Delay WOUV...DC Series
2
4 3/ 2 2 1/ 3
180 160 140 120 100 80 60 40
Drop-Out Time Delay, WOUV DC Series
Trip Setting: O/V - 110% U/V - 90%
13/64" DIA. 4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
20 0 0 20 40 60 80 Time Delay (msec) 100 120 140
PART NUMBER SELECTION
Sample Part No. WOUV-12DC-A Type: WOUV - Over/Undervoltage Line Voltage VDC 125DC 12DC 18DC 240DC 250DC 24DC 305DC 28DC 405DC 32DC 430DC 48DC 470DC 60DC 120DC 560DC Options: Blank - Standard A = 2 Form A Contacts B = 2 Form B Contacts H = 125 VDC Contacts P = Transient Protection Transient Protection - All voltage relays will withstand momentary voltage surges of twice the nominal rated input voltage (standard). Option "P" provides additional transient protection which complies with the requirements of ANSI/IEEE C37.90-1978 Consult factory for additional models.
23
PRODUCT SPECIFICATIONS
Part Number
Nominal Voltage (10%) ................. Drop-out Point (u/v models) ........... Pick-Up Point (o/v models) ............. Output Contacts ............................... Contact Ratings ................................ Operating Temperature Range ........ Temperature Effects ......................... Power Consumption ........................
WOUV
12 VDC to 560 VDC 70-100% of nominal voltage, screwdriver adjustable 100-125% of nominal voltage, screwdriver adjustable One set N.O., One set N.C. 5 amp resistive at 120 VAC or 28 VDC -40C to +75C Less than 1% voltage drift over the temperature range. 12 to 60 VDC models: 1 W max. 120 to 305 VDC models: 2 W max. 405 to 470 VDC models: 3 W max. 560 VDC Model: 4 W max. A short duration delay is provided to prevent nuisance tripping due to momentary dips or surges in voltage. The drop-out delay, following a voltage fault is 75 to 100 milliseconds
Time Delay ........................................
Notes: 1. Remove black screws for access to the O/V and U/V trip adjustment. 2. Clockwise rotation of the adjustment potentiometer will raise the voltage trip point. 3. The adjustments are by means of a single turn potentiometer. Use a small screwdriver and do not force beyond the limit stops.
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)


▲Up To Search▲   

 
Price & Availability of WOUV-12DC-A

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X